134
2600T SERIES |  PRESSURE TRANSMITTERS |  OI/266/FF-EN REV. E
Certificate IECEx Ex ic IIC T4/T5/T6 Gc and                                      
Ex tc IIIC T85°C Dc, Ta = -50°C to +75°C
IECEx certificate number IECEx FME 16.0004X (Tremezzina, 
Warminster, Bangalore and Shanghai products)
The other marking refers to the protection type used according
to relevant EN standards:
•  Ex ic: Intrinsic safety, protection level “c”
•  IIC: gas group
•  T4: Temperature class of the transmitter (which corresponds 
to 135°C max) with a Ta from -50°C to +85°C
•  T5: Temperature class of the transmitter (which corresponds 
to 100°C max) with a Ta from -50°C to +40°C
•  T6: Temperature class of the transmitter (which corresponds 
to 85°C max) with a Ta from -50°C to +40°C
•  Ex tc: type of protection “tc” means protection by enclosure 
technique
About the applications, this transmitter can be used in Zone 2 
(Gas) and in Zone 22 (Dust) (unlikely/infrequent hazard) as it 
shown on the following sketches..
Application with Dust
Application for pressure transmitter Ex ic categories 3 Gc and 3 Dc
d) Certificate ATEX II 3 G Ex ic IIC T4/T5/T6 Gc and                          
II 3 D Ex tc IIIC T85°C Dc, Ta = -50°C to +75°C
FM Approvals Certificate number FM09ATEX0025X 
(Tremezzina, Warminster, Bangalore and Shanghai products)
The meaning of Atex code is as follows :
•  II: Group for surface areas (not mines)
•  3: Category of equipment
•  G: Gas (dangerous media)
•  D: Dust (dangerous media)
•  T85°C: Maximum surface temperature of the transmitter 
enclosure with a Ta from -50°C to +40°C for Dust (not Gas).
IMPORTANT 
It is the technical support for the ABB Declaration of 
Conformity.
IMPORTANT 
When installed this transmitter must be supplied by a 
voltage limiting device which will prevent the rated voltage 
of 32 V d.c. being exceeded.
Application with Gas
IMPORTANT 
Note for pressure transmitter with combined approval. Before installation of the Transmitter, the customer should permanently 
mark his chosen Protection Concept on the safety label. The transmitter can only be used with according to this Protection 
Concept for the whole life. If two or more types of protection box (on safety label) are permanent marked, the pressure 
transmitter must be removed from hazardous classified locations. The selected Type of Protection is allowed to be changed 
only by manufacturer after a new satisfactory assessment.
Note: the transmitter 
must be connected to a 
supply with 32 V d.c. max 
output voltage as above 
indicated. 
Zone 2
266 Tx Category 3 G Ex ic 
Note: the protection is 
mainly assured by the “IP” 
degree associated to the 
low power from supply.
Zone 22
266 Tx Category 3 D IP6x Ex tc