82
2600T SERIES | PRESSURE TRANSMITTERS | OI/266/FF-EN REV. E
...Equations
Depending by the L_TYPE selection the following signal conversions are applied:
Configuration hints
The minimum configuration for having the AI working and/or moving out from the OOS needs at least the following settings:
• CHANNEL different by 0 (uninitialized)
• XD_SCALE = OUT_SCALE
• L_TYPE = Direct
** The minimum configuration can be set also via the RB_SPECIAL_RESTART
L_TYPE Formula
Direct PV = CHANNEL_VALUE
Indirect
This conversion is applied when the XD_SCALE values are different from the OUT_SCALE values
Indirect Square Root
ELSE IF FIELD_VAL < LOW_CUT
ELSE
PV = √