Note: The UL Listing of drive and MMP combinations applies only to drives that are
mounted in appropriately sized metal enclosures that are capable of containing any
drive component failure. Wall-mounted drives with UL Type 1 kits (optional) are not
covered by the UL combination listing of drives with MMPs.
WARNING!
Use fuses for the short-circuit protection of a wall-mounted drive with the UL Type
1 kit (optional). Serious injury, fire, or damage to equipment can result from the
use of MMPs instead of fuses.
Minimum enclosure volume
4)
MMP type
1) 2) 3)
Frame
UL (NEC) type
ACH480-04-…
in
3
dm
3
3-phase U
N
= 480 V
148224.3
MS132-6.3 & S1-M3-25
5)
R102A1-4
148224.3
MS132-6.3 & S1-M3-25
5)
R103A0-4
148224.3
MS132-10 & S1-M3-25
5)
R103A5-4
148224.3
MS132-10 & S1-M3-25
5)
R104A8-4
148224.3MS165-16R106A0-4
148224.3MS165-16R107A6-4
148224.3MS165-20R2011A-4
148224.3MS165-32R3014A-4
148224.3MS165-42R3021A-4
457775.0MS165-54R4027A-4
457775.0MS165-65R4034A-4
457775.0MS5100-100 / MS165-80R4042A-4
1)
All manual motor protectors listed are Type E self-protected up to 65 kA, except MS165-80 which is Type E
self-protected up to 50 kA. See the ABB manual motor starter catalog (1SBC100214C0201) for complete
technical data on the ABB Type E manual motor protectors. In order for these manual motor protectors to be
used for branch circuit protection, they must be UL listed Type E manual motor protectors, otherwise they
can be used only as an At Motor Disconnect. “At Motor Disconnect” is a disconnect just ahead of the motor
on the load side of the panel.
2)
480Y/277 V delta systems only: Short-circuit protective devices with slash voltage ratings (e.g. 480Y/277 V
AC) can be applied only in solidly grounded networks where the voltage from line-to-ground does not exceed
the lower of the two ratings (e.g. 277 V AC), and the voltage from line-to-line does not exceed the higher of
the two ratings (e.g. 480 V AC). The lower rating represents the device’s interrupting capability per pole.
3)
Manual motor protectors may require adjusting the trip limit from the factory setting at or above the drive input
Amps to avoid nuisance tripping. If the manual motor protector is set to the maximum current trip level and
nuisance tripping is occurring, select the next size MMP. (MS132-10 is the highest size in the MS132 frame
size to meet Type E at 65 kA; the next size up is MS165-16.)
4)
For all drives, the enclosure must be sized to accommodate the specific thermal considerations of the
application as well as provide free space for cooling. Refer to the technical data. For UL only: The minimum
enclosure volume is specified in the UL listing when applied with the ABB Type E MMP shown in the table.
Fuses must be used for wall-mounted drives installed with a UL Type 1 kit.
5)
Requires the use of the S1-M3-25 line side feeder terminal with the manual motor protector to meet Type E
self-protection class.
136 Technical data