Installation checklist and start-up
110
ACS800-17-specific parameters in the IGBT Supply Control Program
The signals and parameters described in the tables below are included in the IGBT
Supply Control Program.
Terms and abbreviations
On-load checks
Start-up and validate these safety functions (if present):
• +Q950 (Prevention of unexpected start-up)
• +Q951 (Emergency stop, Category 0)
• +Q952 (Emergency stop, Category 1)
• +Q963 (Emergency stop, Category 0)
• +Q964 (Emergency stop, Category 1)
• +Q968 (Safe torque off with a safety relay).
Optional functions. See:
- Safety options for ACS800 cabinet-
installed drives (+Q950, +Q951,
+Q952, +Q963, +Q964, +Q967 and
+Q968): Wiring, start-up and
operation instructions
(3AUA0000026238 [English])
- delivery-specific circuit diagrams.
Check the functioning of the ATEX-certified thermal motor protection
function (+Q971, if present).
Optional function. See:
- ATEX-certified thermal motor
protection functions for ACS800
cabinet-installed drives
(+L513+Q971 and +L514+Q971):
Safety, wiring, start-up and operation
instructions (3AUA0000082378
[English]).
- delivery-specific circuit diagrams.
Check that the cooling fans rotate freely in the right direction, and the air
flows upwards.
Check visually that the fans rotate in
the direction indicated by an arrow
on the fan housing.
Check the direction of rotation of the motor.
Term Definition
B Boolean
C Character string
Def. Default value
FbEq Fieldbus equivalent: the scaling between the value shown on the control
panel and the integer used in serial communication
I Integer
R Real
T. Data type (see B, C, I, R)
Action Additional information