EasyManua.ls Logo

ABB ACS800-17 - Cabinet Fan Replacement (Frame 2 Xr8 I and up with IP21-42)

ABB ACS800-17
236 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
124
Cabinet fan replacement (Frame 2xR8i and up with IP21-42)
WARNING! Read and follow the instructions in chapter Safety instructions. Ignoring
the instructions can cause physical injury or death, or damage to the equipment.
1. Switch off the power to the unit and open the main disconnecting device. Close
the grounding switch (option +F259) if there is one.
2. Let the intermediate circuit DC capacitors discharge for five minutes. Ensure by
measuring that the drive is not live
before starting the work.
3. Remove the grating (A) and the two fans by undoing the four screws (B).
4. If necessary, undo the four screws (C) to remove the airflow guide (D).
B
B
C
C
A
D