Electrical installation
90
Motor connection – Frame R8i units without option +E202 or +H359
Connection diagram
Connection procedure
1. Open the door of the input/output cubicle (see section Cabling direction starting on
page 33).
2. Remove any shrouds that protect the output busbars and cable entries.
3. Lead the cables into the inside of the cubicle. It is recommended to apply 36
grounding of the cable shields at the entry as shown below.
4. Connect the cables as follows:
Twist the cable shields into bundles and connect to cabinet PE (ground) busbar.
Connect any separate ground conductors or cables to cabinet PE (ground)
busbar.
Connect the phase conductors to the output power terminals (U2, V2, W2). For
the tightening torques, see chapter Technical data.
5. Provide support for the cables whenever necessary.
6. Refit all shrouds removed earlier and close the door.
U2
V2
W2
PE
M
3~
U1
W1
V1
PE
Supply and inverter unit cubicle
Input/output cubicle