Technical data
136
Symbols
Derating
The load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres
(3281 ft), or if the ambient temperature exceeds 40 °C (104 °F).
ACS800-17-1640-5 1746 1884 2734 1400 1809 1300 1409 1000 52 10240 78
ACS800-17-2160-5 2304 2486 3608 1800 2387 1700 1860 1300 68 12800 79
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V, or 690 V
ACS800-17-0060-7 53 57 86 55 54 45 43 37 1.8 500 73
ACS800-17-0070-7 73 79 120 75 75 55 60 55 2.4 500 73
ACS800-17-0100-7 86 93 142 90 88 75 71 55 2.8 500 73
ACS800-17-0160-7 119 132 192 110 127 110 99 90 7 1300 74
ACS800-17-0200-7 135 150 218 132 144 132 112 90 8 1300 74
ACS800-17-0260-7 180 201 301 200 193 160 150 132 11 3160 75
ACS800-17-0320-7 250 279 417 250 268 250 209 200 12 3160 75
ACS800-17-0400-7 300 335 502 315 322 250 251 200 16 3160 75
ACS800-17-0440-7 344 382 571 355 367 355 286 270 17 3160 75
ACS800-17-0540-7 400 447 668 450 429 400 334 315 18 3160 75
ACS800-17-0790-7 593 659 985 630 632 630 493 450 33 6400 77
ACS800-17-0870-7 657 729 1091 710 700 710 545 500 32 6400 77
ACS800-17-1050-7 784 876 1310 900 840 800 655 630 36 6400 77
ACS800-17-1330-7 1001 1112 1663 1120 1067 1120 831 800 48 10240 78
ACS800-17-1510-7 1164 1256 1879 1250 1206 1200 940 900 51 10240 78
ACS800-17-1980-7 1536 1657 2480 1700 1591 1600 1240 1200 67 12800 79
ACS800-17-2780-7 2091 2321 3472 2300 2228 2300 1736 1600 94 17920 79
ACS800-17-2940-7 2280 2460 3680 2500 2362 2400 1840 1800 99 19200 79
(1) 156 A allowed at 460 V
(2) 240 A allowed at 460 V
(3) 302 A allowed at 460 V
(4) 361 A allowed at 460 V
PDM-184674-E51
Nominal ratings
I
1N
Nominal input current
I
cont.max
Continuous RMS output current. No overloadability at 40 °C (104 °F).
I
max
Maximum output current. Allowable for 10 seconds at start, otherwise as long as allowed
by drive temperature.
Typical ratings for no-overload use
P
cont.max
Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Typical ratings for light-overload use (10% overloadability)
I
2N
Continuous rms current. 10% overload is allowed for 1 minute every 5 minutes.
P
N
Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Typical ratings for heavy-duty use (50% overloadability)
I
2hd
Continuous rms current. 50% overload is allowed for 1 minute every 5 minutes.
P
hd
Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
ACS800-17 type
Nominal ratings
No-over-
load use
Light-
overload use
Heavy-duty
use
Heat dissi-
pation
Air
flow
Noise
level
I
1N
A
I
cont.max
A
I
max
A
P
cont.max
kW
I
2N
A
P
N
kW
I
2hd
A
P
hd
kW kW m
3
/h dBA