Planning the electrical installation
65
explosion-safe (EX) motors. Failure of the motor to fulfil the following requirements
or improper installation may shorten motor life or damage the motor bearings.
* manufactured before 1.1.1998
** For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer.
*** If the intermediate DC circuit voltage of the drive will be increased from the nominal level by resistor braking or
by the IGBT supply unit control program (parameter selectable function), check with the motor manufacturer if
additional output filters are needed in the applied drive operation range.
Manufacturer
Motor type Nominal mains
voltage (AC line
voltage)
Requirement for
Motor insulation
system
ABB du/dt filter, insulated N-end bearing and ABB common mode
filter
P
N
< 100 kW
and
frame size < IEC 315
100 kW <
P
N
< 350 kW
or
frame size >
IEC 315
P
N
> 350 kW
or
frame size >
IEC 400
P
N
< 134 hp
and frame size
<NEMA500
134 hp <
P
N
< 469 hp
or frame size
>
NEMA 500
P
N
> 469 hp
or frame size
>NEMA580
A
B
B
Random-
wound M2_
and M3_
U
N
< 500 V Standard - + N + N + CMF
500 V < U
N
< 600 V Standard + du/dt + du/dt + N + du/dt + N + CMF
or
Reinforced - + N + N + CMF
600 V < U
N
< 690 V Reinforced + du/dt + du/dt + N + du/dt + N + CMF
Form-wound
HX_ and AM_
380 V < U
N
< 690 V Standard n.a. + N + CMF P
N
< 500 kW:
+ N + CMF
P
N
> 500 kW:
+ N + CMF + du/dt
Old* form-
wound HX_
and modular
380 V < U
N
< 690 V Check with the
motor
manufacturer.
+ du/dt with voltages over 500 V + N + CMF
Random-
wound HX_
and AM_ **
0 V < U
N
< 500 V Enamelled wire
with fibre glass
taping
+ N + CMF
500 V < U
N
< 690 V + du/dt + N + CMF
N
O
N
-
A
B
B
Random-
wound and
form-wound
U
N
< 420 V Standard: Û
LL
=
1300 V
- + N or CMF + N + CMF
420 V < U
N
< 500 V Standard: Û
LL
=
1300 V
+ du/dt + du/dt + N + du/dt + N + CMF
or
+ du/dt + CMF
or
Reinforced: Û
LL
=
1600 V, 0.2 µs
rise time
- + N or CMF + N + CMF
500 V < U
N
< 600 V Reinforced: Û
LL
=
1600 V
+ du/dt + du/dt + N + du/dt + N + CMF
or
+ du/dt + CMF
or
Reinforced: Û
LL
=
1800 V
- + N or CMF + N + CMF
600 V < U
N
< 690 V Reinforced: Û
LL
=
1800 V
+ du/dt + du/dt + N + du/dt + N + CMF
Reinforced: Û
LL
=
2000 V, 0.3 µs
rise time ***
- N + CMF N + CMF