Technical data
124
Symbols
ACS800-37-1820-5 2037 2956 1400 1956 1300 1524 1000 67 10240 78
ACS800-37-2200-5 2529 3670 1800 2428 1700 1892 1350 81 12800 79
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V, or 690 V
ACS800-37-0170-7 139 202 132 133 110 104 90 8 1300 74
ACS800-37-0210-7 162 235 160 156 132 121 110 9 1300 74
ACS800-37-0260-7 201 301 200 193 160 150 132 12 3160 75
ACS800-37-0320-7 279 417 250 268 250 209 200 15 3160 75
ACS800-37-0400-7 335 502 315 322 250 251 200 18 3160 75
ACS800-37-0440-7 382 571 355 367 355 286 270 19 3160 75
ACS800-37-0540-7 447 668 450 429 400 334 315 21 3160 75
ACS800-37-0790-7 659 985 630 632 630 493 450 35 6400 77
ACS800-37-0870-7 729 1091 710 700 710 545 500 37 6400 77
ACS800-37-1160-7 953 1425 900 914 900 713 710 46 6400 77
ACS800-37-1330-7 1112 1663 1120 1067 1120 831 800 54 10240 78
ACS800-37-1510-7 1256 1879 1250 1206 1200 940 900 62 10240 78
ACS800-37-2320-7 1866 2791 1800 1791 1750 1396 1400 89 12800 79
ACS800-37-2780-7 2321 3472 2300 2228 2300 1736 1600 106 17920 79
ACS800-37-3310-7 2665 3987 2700 2559 2600 1999 2000 121 19200 79
1) 156 A allowed at 460 V
2) 240 A allowed at 460 V
3) 302 A allowed at 460 V
4) 361 A allowed at 460 V
PDM-184674-G5
Nominal ratings
I
cont.max
Continuous RMS output current. No overloadability at 40 °C (104 °F).
I
max
Maximum output current. Allowable for 10 seconds at start, otherwise as long as allowed
by drive temperature.
Typical ratings for no-overload use
P
cont.max
Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Typical ratings for light-overload use (10% overloadability)
I
2N
Continuous rms current. 10% overload is allowed for 1 minute every 5 minutes.
P
N
Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Typical ratings for heavy-duty use (50% overloadability)
I
2hd
Continuous rms current. 50% overload is allowed for 1 minute every 5 minutes.
P
hd
Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
ACS800-37 type
Nominal
ratings
No-over-
load use
Light-
overload use
Heavy-duty
use
Heat dissi-
pation
Air
flow
Noise
level
I
cont.max
A
I
max
A
P
cont.max
kW
I
2N
A
P
N
kW
I
2hd
A
P
hd
kW kW m
3
/h dBA