The ACS800-37
37
Control panel
A control panel (type CDP-312R) is installed on the door of the drive. The CDP-312R
is the user interface of the supply unit (line-side converter) and the inverter unit
(motor-side converter) of the drive, providing the essential controls such as Start/
Stop/Direction/Reset/Reference, and the parameter settings for the units’ application
programs. More information on using the panel can be found in the Firmware Manual
delivered with the drive.
The control panel is wired to both the supply unit and the inverter unit using a
Y-splitter. The unit that is currently being controlled is indicated by the drive name on
the drive display; the suffix “MR” denotes inverter unit, “LR” denotes supply unit. The
control is switched between the units as follows:
To control the supply unit
WARNING! The drive does not stop by pressing the control panel Stop key in local
control mode.
To control the inverter unit…
Step Action Press… Display (example)
1. To enter the Drive Selection Mode
Note: In local control mode, the motor-side converter trips
if parameter 30.02 PANEL LOSS is set to FAULT. Refer to
the appropriate application program firmware manual.
2. To scroll to ID number 2
3. To verify the change to the line-side converter and display
the warning or fault text
Step Action Press… Display (example)
1. To enter the Drive Section Mode
2. To scroll to ID number 1
3. To verify the change to the motor-side converter
DRIVE
ACS 800 0490_3MR
ASXR7xxx
ID-NUMBER 1
ACS 800 0490_3LR
IXXR7xxx
ID-NUMBER 2
ACT
ACS 800 0490_3LR
DC OVERVOLT (3210)
2 -> 380.0 V
** FAULT **
DRIVE
ACS 800 0490_3LR
IXXR7xxx
ID-NUMBER 2
ACS 800 0490_3MR
ACXR7xxx
ID-NUMBER 1
ACT
FREQ 0.00 Hz
CURRENT 0.00 A
POWER 0.00 %
1 L -> 0.0 rpm I