Planning the electrical installation
62
* manufactured before 1.1.1998
** For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer.
*** If the intermediate DC circuit voltage of the drive will be increased from the nominal level by resistor braking or
by the IGBT supply unit control program (parameter selectable function), check with the motor manufacturer if
additional output filters are needed in the applied drive operation range.
Note 1: The abbreviations used in the table are defined below.
Note 2: Explosion-safe (EX) motors
The motor manufacturer should be consulted regarding the construction of the motor insulation and
additional requirements for explosion-safe (EX) motors.
Note 3: High-output motors and IP 23 motors
For motors with higher rated output than what is stated for the particular frame size in EN 50347 (2001)
and for IP 23 motors, the requirements of ABB random-wound motor series M3AA, M3AP, M3BP are
N
O
N
-
A
B
B
Random-
wound and
form-wound
U
N
< 420 V Standard: Û
LL
=
1300 V
- + N or CMF + N + CMF
420 V < U
N
< 500 V Standard: Û
LL
=
1300 V
+ du/dt + du/dt + N + du/dt + N + CMF
or
+ du/dt + CMF
or
Reinforced: Û
LL
=
1600 V, 0.2 µs
rise time
- + N or CMF + N + CMF
500 V < U
N
< 600 V Reinforced: Û
LL
=
1600 V
+ du/dt + du/dt + N + du/dt + N + CMF
or
+ du/dt + CMF
or
Reinforced: Û
LL
=
1800 V
- + N or CMF + N + CMF
600 V < U
N
< 690 V Reinforced: Û
LL
=
1800 V
+ du/dt + du/dt + N + du/dt + N + CMF
Reinforced: Û
LL
=
2000 V, 0.3 µs
rise time ***
- N + CMF N + CMF
Abbreviation Definition
U
N
nominal voltage of the supply network
Û
LL
peak line-to-line voltage at motor terminals which the motor insulation must withstand
P
N
motor nominal power
du/dt du/dt filtering at the output of the drive (+E205)
CMF common mode filtering (+E208)
N N-end bearing: insulated motor non-driven end bearing
n.a. Motors of this power range are not available as standard units. Consult the motor manufacturer.
Manufacturer
Motor type Nominal mains
voltage (AC line
voltage)
Requirement for
Motor insulation
system
ABB du/dt filter, insulated N-end bearing and ABB common mode
filter
P
N
< 100 kW
and
frame size < IEC 315
100 kW <
P
N
< 350 kW
or
frame size >
IEC 315
P
N
> 350 kW
or
frame size >
IEC 400
P
N
< 134 HP
and frame size
<NEMA500
134 HP <
P
N
< 469 HP
or frame size
>
NEMA 500
P
N
> 469 HP
or frame size
>NEMA580