Page #86 background imageLoading...
Page #86 background image
Resistor braking
86
Braking circuit commissioning
For more information, see the appropriate Firmware Manual.
Enable the braking chopper function. Please note that a braking resistor must be
connected when the chopper is enabled
Switch off the overvoltage control of the drive
Adjust any other relevant parameters in group 48.
WARNING! If the drive is equipped with a braking chopper but the chopper is not
enabled by parameter setting, the braking resistor must be disconnected because
the protection against resistor overheating is then not in use.