Page 10/25
100% load
95.6
%
75% load
96.0
%
50% load
96.1
%
25% load
95.8
%
Eco-mode efficiency, linear load
≥ 99.0
%
Crest factor (Load supported)
3: 1
-
Bypass - automatic: static switch
STATIC BYPASS
Type: automatic, static switch in each module
Transfer time: inverter bypass / bypass inverter / in
eco-mode
<1 / <5 / <6
ms
Rated current
800 160
A
Fault clearing capability (bypass mode) for 20 ms
10xIn 10xIn
A
Overload current on bypass mode (< 25°C)
continuously @ 110% load min
STATIC BYPASS
Bypass protection fuse or circuit breaker rating
5x160
A, gL
fuse