Table 2: Recommended AC wiring (copper wires) according to IEC 60950-1, recommended
fuse ratings for slow line fuses (gL) or circuit breakers (CB), connection terminal size and max.
tightening torque.
Single input
Max. rectifier input current with charging batt.
835A at 230V / 875A at 220V
Output
Rated output current in normal conditions
725A at 230V / 758A at 220V
Fuse A
Type: gL or CB
(quantity x A)
Cable A
(quantity x mm
2
)
Type: gL or CB
(only needed in parallel
system)
2
Cable D
(quantity x mm
2
)
500
3 x 1000A
(3 pole, bolded N)
5x(2x240)
5x(3x120)
4 x 800A
(4 pole)
5x(2x240)
5x(3x120)
All connection points are bus-bar, M12. Recommended tightening torque 42 Nm
Table 3: Recommended DC wiring (copper wires) according to IEC 60950-1, recommended
fuse ratings for fast acting fuses (gR) or circuit breakers (CB), connection terminal size and max.
tightening torque.
Type: gR or CB
(quantity x A)
Cable E
(quantity x mm
2
)
100
(one module)
2 x 250A
(2 pole)
2x(1x120) with 40-45 12V battery blocks
2x(1x95) with 46-50 12V battery blocks
All connection points are bus-bar, M8. Recommended tightening torque 24 Nm