Figure 6: Top view and indication of the minimum clearances for UPS + other cabinets in row.
Table 5: Minimum clearances for single UPS or for UPS + other cabinets in row.
A
Back clearance for ventilation
(forced air outlet)
300 mm
B
Front clearance needed to allow
a correct door opening
1000 mm
C Maximum door opening angle 115°
D Top Clearance 400 mm
Side clearance R
0 mm
(not needed)
Side clearance L
0 mm
(not needed)