Modifications reserved
Page 23/94
Table 8: Recommended AC wiring (copper wires) according to IEC 60950-1, recommended
fuse ratings for slow line fuses (gL) or circuit breakers (CB), connection terminal size and max.
tightening torque.
Rated
power
(kW)
Rectifier input
Max. rectifier input current
with battery charging
835A at 230V / 875A at
220V
Bypass input
Max. bypass input current
732A at 230V / 765A at 220V
Output
Rated output current in normal
conditions
725A at 230V / 758A at 220V
Fuse B
Type: gL or CB
(quantity x A)
Cable B
(quantity x
mm
2
)
Fuse C
Type: gL or CB
(quantity x A)
Cable B
(quantity x
mm
2
)
Fuse D
Type: gL or CB
(only needed in
parallel system)
(quantity x mm
2
)
Cable D
(quantity x mm
2
)
500
3 x 1000A
(3 pole, bolded N)
5x(2x240)
5x(3x120)
3 x 800A
(3 pole, bolded N)
5x(2x240)
5x(3x120)
4 x 800A
(4 pole)
5x(2x240)
5x(3x120)
All connection points are bus-bar, M12. Recommended tightening torque 42 Nm
Table 9: Recommended DC wiring (copper wires) according to IEC 60950-1, recommended
fuse ratings for fast acting fuses (gR) or circuit breakers (CB), connection terminal size and max.
tightening torque.
Common battery
Rated power
(kW)
Fuse E
Type: gR or CB
(quantity x A)
Cable E
(quantity x mm
2
)
500
2x1250A
(2 pole)
2x(3x240)
2x(4x150)
All connection points are bus-bar, M12. Recommended tightening torque 42 Nm