Figure 26 Monitoring image
The main characteristics of
WAVEMON Software
are:
Automatic unattended master/slave shutdown in heterogeneous networks
On-screen autonomy time / battery time countdown
On-screen server log off and shutdown procedure
Extensive logging of all UPS activity and power quality data, with timestamp
Scheduled UPS economy mode, service mode, other systems status
Graphical user interface for Windows compatible platforms
Automatic unattended local shutdown
Special software modules to close and save open MS-Office documents.
Compatible for all optional modules like UPSDIALER, SNMP adapters, Temperature
sensors, etc. The UPS-Management Software is a client-/server-application for
networks and local workstations. Basically
WAVEMON-Software
consists of two parts:
the server-module of the UPS-Management Software is
UPSServ
, which communicates
via RS-232 cable with the UPS. Working as a background process the UPSServ collects
messages, received from the UPS. The UPSServ interprets received messages and
makes them available to the client-module
UPSCli
and to any SNMP-based
management station.
When UPSServ detects voltage variations or a power failure it can execute various so called system
„event routines“, which for example may shutdown the server or send warning to connected users.
These system event routines which are a part of the UPS-Management Software can be adjusted to
your demands.
The UPS management software includes with every serial number the licence for using the UPS
service on one server with one UPS and an unlimited numbers of connected WINDOWS workstations.
When operating with two or more servers a licence for every additional server is required. It doesn’t
matter if the UPS service runs at that location or if the server is halted by a UPS service via remote
command. The same regulations are applicable to the use of remote send/receive modules RCCMD
and multiserver shutdown under NT, UNIX and other operating systems. The service programs are