BACNET PRIORITY ARRAY
BACnet uses a command prioritization scheme for objects that control equipment or software parameters
that affect the operation of equipment connected to devices. The use of this command prioritization scheme
(commonly referred to as Priority Array) allows a device to determine the order in which an object is
controlled. Command Prioritization assigns unique levels of priority to the different types of devices that can
write values to a device. There are 16 prioritization levels with Level 1 being highest and Level 16 the lowest.
For example:
Priority Level
Application
Priority Level
Application
1
Manual-Life Safety
9
Available
2
Automatic-Life Safety
10
Available
3
Available
11
Available
4
Available
12
Available
5
Critical Equip. Control
13
Available
6
Minimum On/Off
14
Available
7
Available
15
Available
8
Manual Operator
16
Available
BACnet defines the types of objects that are either required or may optionally support the command
prioritization scheme.