EasyManuals Logo

ABB Cylon FBXi Series User Manual

ABB Cylon FBXi Series
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #77 background imageLoading...
Page #77 background image
FBXi Series | FBXi Operation
©ABB 2023 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
77
OUTPUT MODES
UniPut terminals can generate an output as follows:
Analog Output 0 ... 10 V, 20 mA, 12-bit resolution
Digital Output 0 ... 10 V, 20 mA
Relay Contacts with ability to switch up to 24 V AC
Maximum Load: 24 V AC, 2 (1) A resistive (inductive) for all relay contacts
Analog 0 … 10 V output mode
In Analog 0 ... 10 V output Mode, the Uniputs configure themselves like this:
where the D/A is the digital to analog converter. All circuitry is fully protected
against 24 V AC.
Digital 0 … 10 V output mode
In Digital 0 ... 10 V output Mode, the Uniputs configure in the same way as
for analog:
In this mode the output toggles between the voltages defined as ON” and OFF”.
Relay Mode
In Relay mode the Uniputs are configured with a
single relay common for each half of the
terminals: