RESTARTING, RESETTING AND UPGRADING THE FBXi
The FBXi controller can be restarted or reset using the two buttons located on the front panel (under the
flap) marked SW1 and SW2 . Beside these buttons there are two LEDs marked L1 and L2 , which are used to
signal the progress of the reset or upgrade:
RESETTING THE WEBUI LOGIN
If the WebUI username / password or IP address have been changed to unknown values so that you cannot
log in to the WebUI, you can reset them to known values, i.e. the Factory defaults:
username:
admin
password:
cylonctl
IP address: based on serial number (see
Configuring the IP connection
on page 39)
To reset the IP address and password, press SW1 while the controller is running, hold it until LED L2 lights up,
and then release SW1.
FULL FACTORY RESET
To restore all settings in the FBXi, including any strategy configuration, the shipped version of firmware,
controller IP address and the WebUI username / password : press SW1 while the controller is booting, hold it
until the LED lights up, and then release SW1.
During Factory reset, LED L2 will indicate the progress as follows:
Slow blink: Reset in progress
Solid colour: Reset successful. Power-cycle the controller to activate.
Fast blink: Reset failed
UPGRADE FIRMWARE FROM USB
insert a FAT-formatted USB drive containing valid firmware (.swu) into either of the USB ports, while the
controller is booting hold SW1 until LED L1 lights up, then release SW1.
During USB upgrade, LED L1 will indicate the progress as follows:
Slow blink: Upgrade in progress
Solid colour: Upgrade successful. Power-cycle the controller to activate.
Fast blink: Upgrade failed
RESTARTING THE CONTROLLER WITHOUT POWER CYCLING
To restart the FBXi without disconnecting the power, press SW2 while the controller is running, hold it until
LED L2 lights up, and then release SW2