FBXi Series | Installation
©ABB 2023 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
48
If the FBXi device is to act as a BBMD (allowing BACnet communication between Ethernet subnets), enter the
relevant parameters on the BBMD/NAT page:
(see
BACnet IP Broadcast Management Device (BBMD)
on page 17 for more detail)
Note: The MS/TP baud rate must match on all devices on the MS/TP subnet. For the FBXi this is set in the RS485
Port > Configuration page (see page 28)
Note: An FBXi cannot have both BACnet MS/TP trunk and a Modbus RTU trunk simultaneously, but an FBXi
controller that has an MS/TP subnet can read and write points to Modbus devices over IP.