FBXi Series | Installation
©ABB 2023 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
67
Add strategy blocks and points to create the required strategy see
MAN0133 CXpro
ᴴᴰ
User Guide
for more detail.
Note: In FBXi-X48 controllers there are:
A total of 2500 strategy blocks, numbered
1
-
2500
A maximum of 1200 exposed BACnet points
A minimum of 0 and a maximum of 48 hardware points:
The 16 points in an attached FLX with MS/TP address set to 0” are numbered 1 16
The 16 points in an attached FLX with MS/TP address set to 1are numbered 101 116
The 16 points in an attached FLX with MS/TP address set to 2are numbered 201 216
In FBXi-X256 controllers there are:
A total of 5000 strategy blocks, numbered
1
-
5000
A maximum of 2500 exposed BACnet points
A minimum of 0 and a maximum of 256 hardware points:
The 16 points in an attached FLX with MS/TP address set to 0” are numbered 1 16
The 16 points in an attached FLX with MS/TP address set to 1are numbered 101 116
The 16 points in an attached FLX with MS/TP address set to 2are numbered 201 216
The 16 points in an attached FLX with MS/TP address set to 3are numbered 301 316
The 16 points in an attached FLX with MS/TP address set to 4are numbered 401 416
The 16 points in an attached FLX with MS/TP address set to 5are numbered 501 516
The 16 points in an attached FLX with MS/TP address set to 6are numbered 601 616
The 16 points in an attached FLX with MS/TP address set to 7are numbered 701 716
The 16 points in an attached FLX with MS/TP address set to 8are numbered 801 816
The 16 points in an attached FLX with MS/TP address set to 9are numbered 901 916
The 16 points in an attached FLX with MS/TP address set to 10are numbered 1001 1016
The 16 points in an attached FLX with MS/TP address set to 11are numbered 1101 1116
The 16 points in an attached FLX with MS/TP address set to 12are numbered 1201 1216
The 16 points in an attached FLX with MS/TP address set to 13are numbered 1301 1316
The 16 points in an attached FLX with MS/TP address set to 14are numbered 1401 1416
The 16 points in an attached FLX with MS/TP address set to 15are numbered 1501 1516
In FBXi-8R8(-H)-X96 controllers there are:
A total of 3500 strategy blocks, numbered
1
-
2500
A maximum of 2500 exposed BACnet points
A minimum of 16 and a maximum of 96 hardware points:
The first 16 are numbered 1 - 16, representing the internal I/O in the FBXi-8R8(-H)-X96
The 16 points in an attached FLX with MS/TP address set to 1are numbered 101 116
The 16 points in an attached FLX with MS/TP address set to 2are numbered 201 216
The 16 points in an attached FLX with MS/TP address set to 3are numbered 301 316
The 16 points in an attached FLX with MS/TP address set to 4are numbered 401 416
The 16 points in an attached FLX with MS/TP address set to 5are numbered 501 516
Note: FLX addresses must be consecutive, starting at 0.