Add strategy blocks and points to create the required strategy – see
MAN0133 CXpro
ᴴᴰ
User Guide
for more detail.
Note: In FBXi-X48 controllers there are:
• A total of 2500 strategy blocks, numbered
1
-
2500
• A maximum of 1200 exposed BACnet points
• A minimum of 0 and a maximum of 48 hardware points:
◦ The 16 points in an attached FLX with MS/TP address set to “0” are numbered 1 … 16
◦ The 16 points in an attached FLX with MS/TP address set to “1” are numbered 101 … 116
◦ The 16 points in an attached FLX with MS/TP address set to “2” are numbered 201 … 216
In FBXi-X256 controllers there are:
• A total of 5000 strategy blocks, numbered
1
-
5000
• A maximum of 2500 exposed BACnet points
• A minimum of 0 and a maximum of 256 hardware points:
◦ The 16 points in an attached FLX with MS/TP address set to “0” are numbered 1 … 16
◦ The 16 points in an attached FLX with MS/TP address set to “1” are numbered 101 … 116
◦ The 16 points in an attached FLX with MS/TP address set to “2” are numbered 201 … 216
◦ The 16 points in an attached FLX with MS/TP address set to “3” are numbered 301 … 316
◦ The 16 points in an attached FLX with MS/TP address set to “4” are numbered 401 … 416
◦ The 16 points in an attached FLX with MS/TP address set to “5” are numbered 501 … 516
◦ The 16 points in an attached FLX with MS/TP address set to “6” are numbered 601 … 616
◦ The 16 points in an attached FLX with MS/TP address set to “7” are numbered 701 … 716
◦ The 16 points in an attached FLX with MS/TP address set to “8” are numbered 801 … 816
◦ The 16 points in an attached FLX with MS/TP address set to “9” are numbered 901 … 916
◦ The 16 points in an attached FLX with MS/TP address set to “10” are numbered 1001 … 1016
◦ The 16 points in an attached FLX with MS/TP address set to “11” are numbered 1101 … 1116
◦ The 16 points in an attached FLX with MS/TP address set to “12” are numbered 1201 … 1216
◦ The 16 points in an attached FLX with MS/TP address set to “13” are numbered 1301 … 1316
◦ The 16 points in an attached FLX with MS/TP address set to “14” are numbered 1401 … 1416
◦ The 16 points in an attached FLX with MS/TP address set to “15” are numbered 1501 … 1516
In FBXi-8R8(-H)-X96 controllers there are:
• A total of 3500 strategy blocks, numbered
1
-
2500
• A maximum of 2500 exposed BACnet points
• A minimum of 16 and a maximum of 96 hardware points:
◦ The first 16 are numbered 1 - 16, representing the internal I/O in the FBXi-8R8(-H)-X96
◦ The 16 points in an attached FLX with MS/TP address set to “1” are numbered 101 … 116
◦ The 16 points in an attached FLX with MS/TP address set to “2” are numbered 201 … 216
◦ The 16 points in an attached FLX with MS/TP address set to “3” are numbered 301 … 316
◦ The 16 points in an attached FLX with MS/TP address set to “4” are numbered 401 … 416
◦ The 16 points in an attached FLX with MS/TP address set to “5” are numbered 501 … 516
Note: FLX addresses must be consecutive, starting at 0.