FBXi Series | FBXi Operation
©ABB 2023 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
71
WIRING
FBXi-X256, FBXi-X48
FBXi-8R8-X96, FBXi-8R8-H-X96
Ground
Common
Point Numbers
Terminal Numbers
Relay Common
(24 V only)
CAUTION - DANGER OF EXPLOSION IF BATTERY IS INCORRECTLY REPLACED.
REPLACE ONLY WITH THE SAME OR EQUIVALENT TYPE RECOMMENDED BY THE MANUFACTURER.
DISPOSE OF USED BATTERIES ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS.
Supply Requirements
24 V AC ±20 % 50/60 Hz
Supply Rating
FBXi-8R8(-H)-X96
30 VA (no FLX modules)
FBXi-8R8(-H)-X96 + 1 x FLX
42 VA
FBXi-8R8(-H)-X96 + 2 x FLX
54 VA
FBXi-8R8(-H)-X96 + 3 x FLX
66 VA
FBXi-X256/FBXi-X48
20 VA (no FLX modules)
FBXi-X256/FBXi-X48 + 1 x FLX
32 VA
FBXi-X256/FBXi-X48 + 2 x FLX
44 VA
FBXi-X256/FBXi-X48 + 3 x FLX
56 VA
FBXi-X256 + 4 x FLX
68 VA
|
|
FBXi-X256 + 16 x FLX
68 VA
FLX Power Connection
Proprietary FLX bus connector carries power and comms from
FBXi Series unit. FBXi can supply power to up to 3 FLX modules.
Auxiliary Power
18 V DC / 60 mA output
BACnet Loading
¼ unit load device