COMMUNICATION INTERFACE CONNECTION TIME SYNCHRONIZATION
1TGC908004M0201 19
5.3. Time Synchronization
In order to provide the correct time and date the Time Sync option must be activated in MNS
Digital Gateway and it may require a time server in the Switchgear Control Network.
The protocol used for time synchronization is the standard Network Time Protocol (NTP).
Time Sync must be activated through the ABB Engineering Tool.
5.3.1. Option 1
A standard network component is installed which can provide the time signal as NTP Server.
Such a NTP Server can be a computer or network server as well as Ethernet switches. As an
option, this NTP Server can be equipped with a GPS Receiver to provide accurate time for the
location.
In case of Option 1, Time Server hardware is not part of MNS and has to be supplied
separately.
If the Time Server is out of service, the MNS Digital Gateway runs with the internal
RTC (Real Time Clock) until a new Time Server signal is available. Redundant Time
Servers are not supported.
Figure 13 Example, showing 3rd party Network Switch and 3rd party NTP Server in a Switch-
gear Control Network