6.3. Handling of redundancy faults
Both MNS Digital Gateway supervise at all times the redundancy conditions, detecting
faults and problems according following table:
Event Action
PLC or DCS connection interrupted for more
than 1 second to Primary MNS Digital Gate-
Redundancy change over if backup MNS
Digital Gateway has an active PLC or DCS
Power loss or internal error of Primary MNS
Digital Gateway
Redundancy change over,
Redundancy error indi-
Power loss of backup MNS Digital Gateway
dancy error indicated
Problems in redundancy setup No change over possible,
Redundancy error indi-
Switchgear Bus at Primary MNS Digital
Gateway disconnected
Redundancy change over
Table 9 Primary and Backup IP address setting
A change over from Primary to Backup MNS Digital Gateway will only be per-
formed if there is no redundancy error.
Nevertheless it is also possible that the DCS/PLC initiates a change over by
sending respective change over command. It needs to be ensured that the
switch over commands are configured in MNS Digital Gateway mapping for
the respective fieldbus.