REDUNDANCY HANDLING OF REDUNDANCY FAULTS
1TGC908004M0201 29
6.3. Handling of redundancy faults
Both MNS Digital Gateway supervise at all times the redundancy conditions, detecting
faults and problems according following table:
Event Action
PLC or DCS connection interrupted for more
than 1 second to Primary MNS Digital Gate-
way
Redundancy change over if backup MNS
Digital Gateway has an active PLC or DCS
c
o
n
n
ection
Power loss or internal error of Primary MNS
Digital Gateway
Redundancy change over,
Redundancy error indi-
cat
e
d
Power loss of backup MNS Digital Gateway
No cha
n
ge
ov
er, Re
d
un-
dancy error indicated
Problems in redundancy setup No change over possible,
Redundancy error indi-
cat
e
d
Switchgear Bus at Primary MNS Digital
Gateway disconnected
Redundancy change over
Table 9 Primary and Backup IP address setting
A change over from Primary to Backup MNS Digital Gateway will only be per-
formed if there is no redundancy error.
Nevertheless it is also possible that the DCS/PLC initiates a change over by
sending respective change over command. It needs to be ensured that the
switch over commands are configured in MNS Digital Gateway mapping for
the respective fieldbus.