DEFAULT DATA MAP DATA MAPPING
54 1TGC908004M0201
9.2.5. Control Commands
Control commands written to the M10x-M handled by the MNS Digital Gateway is possible
utilizing the following function codes and address ranges.
FC06, FC 16 40001 …. 49999 Word registers
The following default Modbus registers must be used for writing control commands
to the M10x via the MNS Digital Gateway.
Modbus
Function
Code
Modbus-
Register
Device Number Modbus Register
Name
Description/Re-
marks
6/16 43001 1 Command Note: content of
the register indi-
cates the com-
mand
6/16 43002 2 Command
6/16
43003
3
Command
6/16
:
:
:
6/16 43128 128 Command
Table 27 Default Modbus Command Registers