REDUNDANCY CONFIGURATION REDUNDANCY
26 1TGC908004M0201
is then available from the Backup MNS Digital Gateway which will become the Primary MNS
Digital Gateway after the switch over.
6.2. Redundancy Configuration
There are three options available to connect DCS or PLC to both MNS Digital Gateway
One DCS / PLC Master connected to both MNS Digital Gateway.
One DCS / PLC with at least redundant (two) master interfaces
Redundant (two) DCS / PLC Master where each is connected to one MNS Digital Gate-
way (see example Figure 21)
6.2.1. Redundant MNS Digital Gateway connection
Both MNS Digital Gateway must be connected via a RS232 Null Modem cable (port Serial 1 on
both MNS Digital Gateway) to enable data synchronization and ensure correct operation
Figure 22 Serial 1 to serial 1 redundant link connections with ferrite core
The length of this cable should not exceed 10 meters
Redun-
dant Link
Cables
2m 1TGE120109R0002
3m 1TGE120109R0003
5m 1TGE120109R0005
10 m 1TGE120109R0010
Ferrite
Core
1TGB000197P0001
Table 6 Serial Redundant Link Cable ordering code