9.2.4. Extended Status Description
In addition to the above within the Default Modbus Map, the following ‘Extended Status’ is
also supported in 4 bytes of data.
Modbus
Function
Code
Modbus-
Register
Device
Number
Modbus Register
Name
Format
3
41001
1
Extended status
2
Byte
3 41002 1 Extended status 2Byte
3
41003
2
Extended status
2
Byte
3
41004
2
Extended status
2
Byte
3 41005 3 Extended status 2Byte
3
4100
3
Extended status
2B
yte
:
:
:
:
:
3 41253 127 Extended status 2 Byte
3
41254
127
Extended status
2
Byte
3
41255
128
Extended status 2 Byte
3 41256 128
Extended status 2 Byte
Table 22 Default Modbus Map Extended Status for M10x-M
The content of the Extended Status ‘Byte 1’ is described in following table:
BYTE 1 Description Remark
Bit
0
Stopped
1
= Motor Stopped or Tripped
Bit
1
Runs
1
= Motor Runs
Bit 2 Runs CW/ Close 1 = Motor Runs, Clockwise
Bit
3
Runs CCW
/Open
1 = Motor Runs, Counter Cloc
kwise
Bit
4
Bit 5
Bit
6
Bit 7 Ready 1 = M10x-M in correct location & main
switch on & no trip & no start inhibit
Table 23 Extended Status Byte 1