REDUNDANCY CONFIGURATION REDUNDANCY
28 1TGC908004M0201
Network addresses must be set for both Primary and Backup MNS Digital Gateway.
Table 8 Primary and Backup IP address setting
It is essential that the IP address setting for LAN 2 of Primary and Backup MNS
Digital Gateway is different (e.g. Primary = 192.168.200.100 / Backup =
192.168.200.101).
The same subnet mask is used because both Ethernet ports are connected to
the same Ethernet network for MView and MNavigate communication.
MNS Digital Gateway LAN3 is not used for M10x applications.
2. Set the slave address for the selected Fieldbus / Field network interface.
Figure 24 MNavigate Fieldbus Slave address Parameterization for Primary and Backup MNS
Digital Gateway