DEFAULT DATA MAP DATA MAPPING
50 1TGC908004M0201
9.2.3. Monitoring with Function Code 03 and 04
Monitoring of the measured (analogue) values from the individual M10x-M is detailed in the
following table.
Modbus
Function
Code
Modbus
Register
Device
Number
Modbus Register
Name
Format Remarks
3 40001 1 Phase current L1
%
Unsigned Int,
2Byte
% age L1 Current
3 40002 1 Thermal image
Unsigned Int, 2
Byte
Used thermal
capacity (only
available if TOL
protection func-
tion is used)
3 40003 1 Time to trip Unsigned Int,
2Byte
Time before
M10x-M will trip
the motor (only
available if TOL
protection func-
tion is used)
3 40004 1 Time to reset Unsigned Int,
2Byte
Time required be-
fore reset allowed
(only available if
TOL protection
function is used)
3 40005 2 Phase current L1
%
Unsigned Int,
2
Byte
% age L1 Current
3 40006 2 Thermal image Unsigned Int,
2
Byte
Used thermal
capacity
:
:
:
:
:
:
3 40509 128
Phase current L1
%
Unsigned Int,
2Byte
% age L1 Current
3 40510 128
Thermal image Unsigned Int,
2Byte
Used thermal
capacity
3 40511 128
Time to trip Unsigned Int,
2Byte
Time before
M10x-M will trip
the motor
3 40512 128
Time to reset Unsigned Int,
2
Byte
Time required be-
fore reset allow
ed
Table 21 Default Modbus Map Measured Values of M10x-M