DATA MAPPING DEFAULT DATA MAP
1TGC908004M0201 55
9.2.6. Switching Commands
The following table details the commands that are required from the Master (DCS / PLC) to
be sent to the M10x-M in order to control the motor or feeder module.
Operation
Type
Description Modbus
Command
Remarks
Control Access
Remote control 0x2100 M10x-M is controlled
Bus-Local control 0x2104 DCS allows control via
Stop Stop, Open 0x0201 Stops the M10x-M,
Opens contactor K1 for
Contactor Feeder ap-
Start
Start CW
Close (CF)
Open (Act)
Start
Start Clockwise
Close for Contactor Feeder applica-
tion
Open for Actuator application
0x0202 Starts the M10x-M.
Close contactor K1
Start CCW
Close (Close)
Start Counterclockwise
Close for Actuator Application
0x0203 Start the M10x-M
Counterclockwise.
Reset Reset 0x1100 Reset of all trips
Table 28 Switching Commands sent from DCS to MNS Digital Gateway