DATA MAPPING DEFAULT DATA MAP
1TGC908004M0201 53
The content of the Extended Status ‘Byte 4’ is related to the Control Access function, for
more information please refer to the Control Access section within this document.
BYTE
4
Description
Remark
Bit 0 HW -Local M10x-M accepts control commands
from the hardwired inputs on M10x-
M, when the respective Local control
input is set to true.
Bit
1
Reserved
Bit 2 BUS-Local M10x-M accepts control commands
from a device on the switchgear con-
trol network, eg. M
View
.
Bit
3
Reserved
Bit 4 Reserved
Bit
5
Reserve
d
Bit
6
Reserved
Bit 7 Remote M10x-M accepts control commands
from DCS only
Table 26 Extended Status Byte 4