FUNCTION CODE 02 READ INPUT STATUS FUNCTION CODES
40 1TGC908004M0201
Function codes and their relevant address range are shown in the table below.
Function Codes Address / Mapping Area Starting Address used in Modbus
Frame
FC
02
10001
-
19999
0
-
9999
FC
04
30001
-
39999
0
-
9999
FC
03
,
06
,
16
40001
-
49999
0
-
99
99
Table 15 Address ranges of Function Codes
8.2. Function Code 02 – Read Input Status
This function allows the control system to obtain the ON/OFF status of discrete inputs from
the MNS Digital Gateway. With function code 2 following information can be requested.
Life Bits
Status Information
Control Access Information
Alarms
Trips
The valid address range: 10001-19999.
8.3. Function Code 03 – Read Holding Registers
With function code 03, the control system can read the registers that can store the numerical
data, which can be driven to external devices as mentioned below.
Measuring Values
Status as Word-oriented bits
Alarm structure (Warnings/Trips)
The valid address range: 40001-49999
8.4. Function Code 04 – Read Input Registers
Function code 04 obtains the contents of the input registers. These locations receive their
values from devices connected to the I/O structure of field units and can only be referenced,
not altered within the system or via MODBUS as mentioned below.
Status as Word-oriented bits
Alarm structure (Warnings/Trips)
The valid address range: 30001-39999