DATA MAPPING DEFAULT DATA MAP
1TGC908004M0201 59
CA BusLocal will be active if Auto Mode is not set and the Bus Local command bit goes from 0
to 1.
Hardware-Local overrides all other CA Levels. It is not possible for the DCS or MView to take
control when the M10x-M is set to HW-Local.
Recommended procedure for sending control commands for a motor starter
1. Set the M10x-M to "Remote" with the command ā€œ0x2100ā€
2. 2.Set the desired state, "Run Reverse", "Off", "Run Forward" or "Trip Reset"
3. Wait until desired state is shown in motor state (received from Slave).
4. Reset previous command "Run Reverse", "Off", "Run Forward" or "Trip Reset"