TROUBLESHOOTING AND MAINTENANCE MNS DIGITAL GATEWAY LED INDICATION
1TGC908004M0201 61
LED indication Description
Additional Information / Actions
Error in MNS Digital
Gateway XML
Configuration file
Possible cause could be a interrupted or
disturbed communication between
MNavigate and MNS Digital Gateway while
downloading.
Please use MNavigate to download the
MNS Digital Gateway configuration again
Error in MNS Digital
Gateway XML
Parameter file
Possible cause could be a interrupted or
disturbed communication between
MNavigate and MNS Digital Gateway while
downloading.
Please use MNavigate to download the
MNS Digital Gateway parameter again
Internal MNS Digital
Gateway error
MNS Digital Gateway is not able to create
internal database.
Please reboot the MNS Digital Gateway
.
If
that doesn’t resolve the problem use
MNavigate to download the MNS Digital
Gateway configuration again.
XML file missing
During startup MNS Digital Gateway is
checking if all required xml files are
available. In case of a missing file that error
is indicated.
Please use MNavigate to download the
MNS Digital Gateway configuration again.
Network configuration
error
MNS Digital Gateway is not able to
configure the IP settings as mentioned in
configuration file e.g. due to wrong setting
of Default Gateway parameter for that
Ethernet Interface.
Please use MNavigate to check the settings
and download the MNS Digital Gateway
configuration again. If a download is not
possible please use a flash card reader (ref.
to MNavigate Help or MNavigate Manual).