Bay control QCBAY
Local remote LOCREM
Local remote control LOCREMCTRL
SCSWI, SXCBR, QCBAY and SXSWI are logical nodes according to IEC 61850. The
signal flow between these function blocks appears in figure
81. The function Logical node
Interlocking (SCILO) in the figure 81 is the logical node for interlocking.
Control operation can be performed from the local IED HMI. If the administrator has
defined users with the UMT tool, then the local/remote switch is under authority control.
If not, the default (factory) user is the SuperUser that can perform control operations from
the local IED HMI without LogOn. The default position of the local/remote switch is on
remote.
SXCBR
SCSWI
SCILO
(3)
SCSWI
SCILO
(3)
SXSWI
-BKR1
-189
-989
IEC 61850
QCBAY
ANSI10000198_2_en.vsd
52
ANSI10000198 V2 EN
Figure 81: Signal flow between apparatus control function blocks
Section 10 1MRK 511 286-UUS A
Control
214
Application manual