6.10.8 Technical data
Table 90: BRCPTOC technical data
Function
Range or value Accuracy
Minimum phase current for operation (5–100)% of
IBase
± 1.0% of I
r
Unbalance current operation (50-90)% of maximum current ± 2.0% of I
r
Timer (0.00-60.000) s ± 0.5% ± 25 ms
Operate time for start function 35 ms typically -
Reset time for start function 30 ms typically -
Critical impulse time 15 ms typically -
Impulse margin time 10 ms typically -
6.11 Directional over-/under-power protection
GOPPDOP/GUPPDUP
6.11.1 Functionality
The directional over-/under-power protection GOPPDOP/GUPPDUP can be used
wherever a high/low active, reactive or apparent power protection or alarming is
required. The functions can alternatively be used to check the direction of active or
reactive power flow in the power system. There are a number of applications where
such functionality is needed. Some of them are:
detection of reversed active power flow
detection of high reactive power flow
Each function has two steps with definite time delay.
6.11.2 Directional overpower protection GOPPDOP
6.11.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional overpower protection GOPPDOP
P >
2
DOCUMENT172362-IMG158942
V2 EN
32
Section 6 1MRK 511 287-UEN A
Current protection
144
Technical manual