10.13.2 Function block
IEC10000285-1-en.vsd
I103GENCMD
BLOCK ^CMD_OFF
^CMD_ON
IEC10000285 V1 EN
Figure 161: I103GENCMD function block
10.13.3 Signals
Table 251: I103GENCMD Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of command
Table 252: I103GENCMD Output signals
Name Type Description
CMD_OFF BOOLEAN Command output OFF
CMD_ON BOOLEAN Command output ON
10.13.4 Settings
Table 253: I103GENCMD Non group settings (basic)
Name
Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
PulseLength 0.000 - 60.000 s 0.001 0.400 Pulse length
InfNo 1 - 255 - 1 1 Information number for command output
(1-255)
10.14 IED commands with position and select for IEC
60870-5-103 I103POSCMD
10.14.1 Functionality
I103POSCMD has double-point position indicators that are getting the position value
as an integer (for example from the POSITION output of the SCSWI function block)
and sending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE). .The standard does not
define the use of values 0 and 3 . However, when connected to a switching device,
these values are transmitted.