9.2.8 Technical data
Table 160: SDDRFUF technical data
Function
Range or value Accuracy
Operate voltage, zero sequence (1-100)% of UBase ± 1.0% of U
r
Operate current, zero sequence (1–100)% of IBase ± 1.0% of I
r
Operate voltage, negative sequence (1–100)% of UBase ± 0.5% of U
r
Operate current, negative sequence (1–100)% of IBase ± 1.0% of I
r
Operate voltage change level (1–100)% of UBase ± 5.0% of U
r
Operate current change level (1–100)% of IBase ± 5.0% of I
r
Operate phase voltage (1-100)% of UBase ± 0.5% of U
r
Operate phase current (1-100)% of IBase ± 1.0% of I
r
Operate phase dead line voltage (1-100)% of UBase ± 0.5% of U
r
Operate phase dead line current (1-100)% of IBase ± 1.0% of I
r
9.3 Breaker close/trip circuit monitoring TCSSCBR
9.3.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Breaker close/trip circuit monitoring TCSSCBR - -
9.3.2 Functionality
The trip circuit supervision function TCSSCBR is designed to supervise the control
circuit of the circuit breaker. The trip circuit supervision generates a current of
approximately 1 mA through the supervised control circuit. The validity supervision
of a control circuit is provided for power output contacts T1, T2 and T3.
The trip circuit supervision operates after a settable definite operating time and resets
after a settable definite time when the fault disappears.
9.3.3 Function block
GUID-6F85BD70-4D18-4A00-A410-313233025F3A V2 EN
Figure 94: Function block
1MRK 511 287-UEN A Section 9
Secondary system supervision
205
Technical manual