The input of this GOOSE block must be linked in SMT by means of
a cross to receive the binary values.
The implementation for IEC61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the OUTxVAL
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then
the OUTxVAL output will be LOW.
14.5 GOOSE function block to receive a double point
value GOOSEDPRCV
14.5.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
double point value
GOOSEDPRCV - -
14.5.2 Functionality
GOOSEDPRCV is used to receive a double point value using IEC61850 protocol via
GOOSE.
14.5.3 Function block
IEC10000249-1-en.vsd
GOOSEDPRCV
BLOCK ^DPOUT
DATAVALID
COMMVALID
TEST
IEC10000249 V1 EN
Figure 256: GOOSEDPRCV function block
14.5.4 Signals
Table 468: GOOSEDPRCV Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of function
1MRK 511 287-UEN A Section 14
Station communication
531
Technical manual