10.3.5.3 Function block
QCBAY
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD
PSTO
UPD_BLKD
CMD_BLKD
LOC
REM
IEC09000080_1_en.vsd
IEC09000080 V1 EN
Figure 112: QCBAY function block
10.3.5.4 Signals
Table 185: QCBAY Input signals
Name Type Default Description
LR_OFF BOOLEAN 0 External Local/Remote switch is in Off position
LR_LOC BOOLEAN 0 External Local/Remote switch is in Local position
LR_REM BOOLEAN 0 External Local/Remote switch is in Remote
position
LR_VALID BOOLEAN 0 Data representing the L/R switch position is valid
BL_UPD BOOLEAN 0 Steady signal to block the position updates
BL_CMD BOOLEAN 0 Steady signal to block the command
Table 186: QCBAY Output signals
Name
Type Description
PSTO INTEGER Value for the operator place allocation
UPD_BLKD BOOLEAN Update of position is blocked
CMD_BLKD BOOLEAN Function is blocked for commands
LOC BOOLEAN Local operation allowed
REM BOOLEAN Remote operation allowed
10.3.5.5 Settings
Table 187: QCBAY Non group settings (basic)
Name
Values (Range) Unit Step Default Description
AllPSTOValid Priority
No priority
- - Priority Priority of originators
1MRK 511 287-UEN A Section 10
Control
243
Technical manual