12.14.8 Technical data
Table 412: LMBRFLO technical data
Function
Value or range Accuracy
Reactive and resistive reach (0.001-1500.000) Ω/phase ± 2.0% static accuracy
± 2.0% degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x U
r
Current range: (0.5-30) x I
r
Phase selection
According to input signals -
Maximum number of fault
locations
100 -
12.15 Station battery supervision SPVNZBAT
12.15.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Station battery supervision function SPVNZBAT U<> -
12.15.2 Function block
GUID-2D3C21EA-75E9-4E44-AA0F-4DEA7599182A V1 EN
Figure 226: Function block
12.15.3 Functionality
The station battery supervision function SPVNZBAT is used for monitoring battery
terminal voltage.
SPVNZBAT activates the start and alarm outputs when the battery terminal voltage
exceeds the set upper limit or drops below the set lower limit. A time delay for the
overvoltage and undervoltage alarms can be set according to definite time
characteristics.
SPVNZBAT operates after a settable operate time and resets when the battery
undervoltage or overvoltage condition disappears after settable reset time.
Section 12 1MRK 511 287-UEN A
Monitoring
480
Technical manual