The input of this GOOSE block must be linked in SMT by means of
a cross to receive the integer values.
The implementation for IEC61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the
DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
14.7 GOOSE function block to receive a measurand value
GOOSEMVRCV
14.7.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
measurand value
GOOSEMVRCV - -
14.7.2 Functionality
GOOSEMVRCV is used to receive measured value using IEC61850 protocol via
GOOSE.
14.7.3 Function block
IEC10000251-1-en.vsd
GOOSEMVRCV
BLOCK ^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251 V1 EN
Figure 258: GOOSEMVRCV function block
14.7.4 Signals
Table 474: GOOSEMVRCV Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of function
Section 14 1MRK 511 287-UEN A