12.15.4 Signals
Table 413: SPVNZBAT Input signals
Name
Type Default Description
U_BATT REAL 0.00 Battery terminal voltage that has to be supervised
BLOCK BOOLEAN 0 Blocks all the output signals of the function
Table 414: SPVNZBAT Output signals
Name Type Description
AL_ULOW BOOLEAN Alarm when voltage has been below low limit for a
set time
AL_UHI BOOLEAN Alarm when voltage has exceeded high limit for a
set time
ST_ULOW BOOLEAN Start signal when battery voltage drops below
lower limit
ST_UHI BOOLEAN Start signal when battery voltage exceeds upper
limit
12.15.5 Settings
Table 415: SPVNZBAT Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation mode Off / On
RtdBattVolt 20.00 - 250.00 V 1.00 110.00 Battery rated voltage
BattVoltLowLim 60 - 140 %Ubat 1 70 Lower limit for the battery terminal voltage
BattVoltHiLim 60 - 140 %Ubat 1 120 Upper limit for the battery terminal voltage
tDelay 0.000 - 60.000 s 0.001 0.200 Delay time for alarm
tReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset of alarm
12.15.6 Measured values
Table 416: SPVNZBAT Measured values
Name
Type Default Description
U_BATT REAL 0.00 Battery terminal voltage that has to be supervised
BLOCK BOOLEAN 0 Blocks all the output signals of the function