12.16.5 Settings
Table 421: SSIMG Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
PressAlmLimit 0.00 - 25.00 - 0.01 5.00 Alarm setting for pressure
PressLOLimit 0.00 - 25.00 - 0.01 3.00 Pressure lockout setting
TempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of the
medium
TempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the medium
tPressureAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for pressure alarm
tPressureLO 0.000 - 60.000 s 0.001 0.000 Time delay for pressure lockout indication
tTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarm
tTempLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for temperture lockout
tResetPressAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for pressure alarm
tResetPressLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for pressure lockout
tResetTempLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture lockout
tResetTempAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture alarm
12.16.6 Operation principle
Insulation gas monitoring function SSIMG is used to monitor gas pressure in the
circuit breaker. Two binary output signals are used from the circuit breaker to initiate
alarm signals, pressure below alarm level and pressure below lockout level. If the
input signal PRES_ALM is high, which indicate that the gas pressure in the circuit
breaker is below alarm level, the function initiates output signal PRES_ALM,
pressure below alarm level, after a set time delay and indicate that maintenance of the
circuit breaker is required. Similarly, if the input signal PRES_LO is high, which
indicate gas pressure in the circuit breaker is below lockout level, the function initiates
output signal PRES_LO, after a time delay. The two time delay settings,
tPressureAlarm and tPressureLO, are included in order not to initiate any alarm for
short sudden changes in the gas pressure. If the gas pressure in the circuit breaker goes
below the levels for more than the set time delays the corresponding signals,
PRES_ALM, pressure below alarm level and PRES_LO, pressure below lockout level
alarm will be obtained.
The input signal BLK_ALM is used to block the two alarms levels. The input signal
BLOCK is used to block both the alarms and the function.
12.16.7 Technical data
Table 422: SSIMG Technical data
Function
Range or value Accuracy
Timers (0.000-60.000) s ± 0.5% ± 110 ms
1MRK 511 287-UEN A Section 12
Monitoring
485
Technical manual