12.18.3 Function block
GUID-365D67A9-BEF8-4351-A828-ED650D5A2CAD V1 EN
Figure 230: SSCBR function block
12.18.4 Signals
Table 427: SSCBR Input signals
Name Type Default Description
I3P GROUP
SIGNAL
- Three phase group signal for current inputs
BLOCK BOOLEAN 0 Block of function
BLK_ALM BOOLEAN 0 Block all the alarms
POSOPEN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/O
ALMPRES BOOLEAN 0 Binary pressure alarm input
LOPRES BOOLEAN 0 Binary pressure input for lockout indication
SPRCHRGN BOOLEAN 0 CB spring charging started input
SPRCHRGD BOOLEAN 0 CB spring charged input
CBCNTRST BOOLEAN 0 Reset input for CB remaining life and operation
counter
IACCRST BOOLEAN 0 Reset accumulated currents power
SPCHTRST BOOLEAN 0 Reset spring charge time
TRVTRST BOOLEAN 0 Reset travel time
Table 428: SSCBR Output signals
Name
Type Description
TRVTOAL BOOLEAN CB open travel time exceeded set value
TRVTCAL BOOLEAN CB close travel time exceeded set value
SPRCHRAL BOOLEAN Spring charging time has crossed the set value
OPRALM BOOLEAN Number of CB operations exceeds alarm limit
OPRLOALM BOOLEAN Number of CB operations exceeds lockout limit
Table continues on next page
1MRK 511 287-UEN A Section 12
Monitoring
489
Technical manual