EasyManua.ls Logo

ABB REC650 - Technical Data

ABB REC650
656 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Synchronization via DNP
The DNP3 communication can be the source for the coarse time synchronization,
while the fine time synchronization needs a source with higher accuracy. See the
communication protocol manual for a detailed description of the DNP3 protocol.
Synchronization via IEC60870-5-103
The IEC60870-5-103 communication can be the source for the coarse time
synchronization, while the fine tuning of the time synchronization needs a source with
higher accuracy. See the communication protocol manual for a detailed description of
the IEC60870-5-103 protocol.
15.2.9 Technical data
Table 497: Time synchronization, time tagging
Function Value
Time tagging resolution, events and sampled measurement values 1 ms
Time tagging error with synchronization once/min (minute pulse
synchronization), events and sampled measurement values
± 1.0 ms typically
Time tagging error with SNTP synchronization, sampled measurement
values
± 1.0 ms typically
15.3 Parameter setting group handling
15.3.1 Functionality
Use the four different groups of settings to optimize the IED operation for different
power system conditions. Creating and switching between fine-tuned setting sets,
either from the local HMI or configurable binary inputs, results in a highly adaptable
IED that can be applied to a variety of power system scenarios.
15.3.2 Setting group handling SETGRPS
15.3.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Setting group handling SETGRPS - -
1MRK 511 287-UEN A Section 15
Basic IED functions
557
Technical manual

Table of Contents