ABB REC650 - Page 238

ABB REC650
656 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AND
OR
AND
From logic for
reclosing
programs
AND
AND OR
AND
t
tSync
"SMBRREC Open
time" timer
Pulse
Blocking out
CBREADY
initiate
SYNC
3PT4TO
3PT3TO
3PT2TO
3PT1TO
OR
AND
t
tReclaim
OR
t
tInhibit
INPROGR
Inhibit (internal)
Blocking out
INHIBIT
Pulse (above)
IEC08000244-2-en.vsd
3PT5TO
Reclaim Timer On
0
CL
COUNTER
Shot 0
R
1
2
3
4
5
Shot 1
Shot 2
Shot 3
Shot 4
Shot 5
LOGIC
reclosing
programs
3PT1
3PT2
3PT3
OR
Shot 0
start
initiate
Shot 1
Shot 2
Shot 3
Shot 4
Shot 5
3PT4
3PT5
t
t1 3Ph
3PT1TO
SMBRREC
State Control
IEC08000244 V2 EN
Figure 104: Reclosing Reclaim and Inhibit timers
Pulsing of the CB closing command
The duration of the pulse is fixed 200 ms. See figure 105
When a reclosing command is issued, the appropriate reclosing operation counter is
incremented. There is a counter for each reclosing shot and one for the total number
of reclosing commands issued.
Section 10 1MRK 511 287-UEN A
Control
232
Technical manual