EasyManua.ls Logo

ABB REC650 - Page 421

ABB REC650
656 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Set value for
parameter
“Mode”
Formula used for complex, three-
phase power calculation
Formula used for voltage and
current magnitude calculation
Comment
4 L1L2
* *
1 2 1 2
( )= × -
L L L L
S U I I
EQUATION1391 V1 EN (Equation 44)
1 2
1 2
( ) / 2
=
= +
L L
L L
U U
I I I
EQUATION1392 V1 EN (Equation 45)
Used when
only U
L1L2
phase-to-
phase
voltage is
available
5
L2L3
* *
2 3 2 3
( )= × -
L L L L
S U I I
EQUATION1393 V1 EN (Equation 46)
2 3
2 3
( ) / 2
=
= +
L L
L L
U U
I I I
EQUATION1394 V1 EN (Equation 47)
Used when
only U
L2L3
phase-to-
phase
voltage is
available
6
L3L1
* *
3 1 3 1
( )= × -
L L L L
S U I I
EQUATION1395 V1 EN (Equation 48)
3 1
3 1
( ) / 2
=
= +
L L
L L
U U
I I I
EQUATION1396 V1 EN (Equation 49)
Used when
only U
L3L1
phase-to-
phase
voltage is
available
7
L1
*
1 1
3= × ×
L L
S U I
EQUATION1397 V1 EN (Equation 50)
1
1
3= ×
=
L
L
U U
I I
EQUATION1398 V1 EN (Equation 51)
Used when
only U
L1
phase-to-
earth voltage
is available
8
L2
*
2 2
3= × ×
L L
S U I
EQUATION1399 V1 EN (Equation 52)
2
2
3= ×
=
L
L
U U
I I
EQUATION1400 V1 EN (Equation 53)
Used when
only U
L2
phase-to-
earth voltage
is available
9
L3
*
3 3
3= × ×
L L
S U I
EQUATION1401 V1 EN (Equation 54)
3
3
3= ×
=
L
L
U U
I I
EQUATION1402 V1 EN (Equation 55)
Used when
only U
L3
phase-to-
earth voltage
is available
* means complex conjugated value
It shall be noted that only in the first two operating modes that is, 1 & 2 the
measurement function calculates exact three-phase power. In other operating modes
that is, from 3 to 9 it calculates the three-phase power under assumption that the power
system is fully symmetrical. Once the complex apparent power is calculated then the
P, Q, S, & PF are calculated in accordance with the following formulas:
Re( )
=P S
EQUATION1403 V1 EN (Equation 56)
Im( )=Q S
EQUATION1404 V1 EN (Equation 57)
1MRK 511 287-UEN A Section 12
Monitoring
415
Technical manual

Table of Contents

Other manuals for ABB REC650