Parameter Values (Range) Unit Step Default Description
Value high limit -10000.0...10000.0     10000.0 Output value high warning limit for
supervision
Value low limit -10000.0...10000.0     -10000.0 Output value low warning limit for
supervision
Value low low limit -10000.0...10000.0     -10000.0 Output value low alarm limit for
supervision
Value deadband 100...100000     1000 Deadband configuration value for
integral calculation. (percentage of
difference between min and max as
0,001 % s)
Table 57: mA input settings
Parameter Values (Range) Unit Step Default Description
Input mode 1=Not in use
5=0..20mA
    1=Not in use Analogue input mode
Input maximum 0...20   1 20 Maximum analogue input value for mA
or resistance scaling
Input minimum 0...20   1 0 Minimum analogue input value for mA or
resistance scaling
Value unit 1=Dimensionless
5=Ampere
23=Degrees
celsius
30=Ohm
    1=Dimensionless Selected unit for output value format
Value maximum -10000.0...10000.0     10000.0 Maximum output value for scaling and
supervision
Value minimum -10000.0...10000.0     -10000.0 Minimum output value for scaling and
supervision
Val high high limit -10000.0...10000.0     10000.0 Output value high alarm limit for
supervision
Value high limit -10000.0...10000.0     10000.0 Output value high warning limit for
supervision
Value low limit -10000.0...10000.0     -10000.0 Output value low warning limit for
supervision
Value low low limit -10000.0...10000.0     -10000.0 Output value low alarm limit for
supervision
Value deadband 100...100000     1000 Deadband configuration value for
integral calculation. (percentage of
difference between min and max as
0,001 % s)
1YHT530004D05 D Section 3
Basic functions
615 series 95
Technical Manual